◆ True double-conversion ◆ DSP technology guarantees high performance ◆ Output power factor 0.8 ◆ Active power factor correction in all phases ◆ ECO mode operation for energy saving ◆ Accepts dual-mains inputs ◆ Emergency power off function (EPO) ◆ Generator compatible ◆ SNMP+USB+ RS232 multiple communications ◆ Adjustable battery numbers ◆ Maintenance bypass available ◆ Optional N+X parallel redundancy ◆ Programmable power management outles

Detail

10KVA ~ 20KVA
Input/Output: 3/3


Features:

◆ True double-conversion
◆ DSP technology guarantees high performance
◆ Output power factor 0.8
◆ Active power factor correction in all phases
◆ ECO mode operation for energy saving
◆ Accepts dual-mains inputs
◆ Emergency power off function (EPO)
◆ Generator compatible
◆ SNMP+USB+ RS232 multiple communications
◆ Adjustable battery numbers
◆ Maintenance bypass available
◆ Optional N+X parallel redundancy
◆ Programmable power management outles
 

 

Technical Parameters

Specification CPTH-2010T CPTH-2015T CPTH-2020T
UPS Rating 10KVA(8KW) 15KVA(12KW) 20KVA(16KW)
AC INPUT Wiring Three Phase (R+S+T+N+G)
RatedVoltage 380Vac
Voltage Range 195~520Vac (50%load); 305~478Vac (100% load)
Frequency Range 46~54Hz
Input Power Factor ≥0.99 (100%Load)
Harmonic current ≤5% (100%Load)
Bypass input Voltage 170Vac~260Vac
Bypass input Frequency 45~54Hz
AC OUTPUT Output Phase Three Phase
Power Rate 0.8
THD 100% Liner load: <2% 100%Non-Liner load: <4%
Output Voltage 3 x 380Vac (3Ph +N)
Frequency AC: Tracking Frequency,Battery mode: 50Hz土0.1%
Peak Rate 3:1
ACfaulty transfertime 0mS
Bypass inverter conversion time 0mS
Frequencytrackingrange

45-54Hz

Frequencytrackingspeed 1S/Hz
Overload 105%-130%: 10mins,130%-150%: 1min,≥150%: 10S
BATTERY Rated Battery Voltage 192VDC/240VDC 192VDC/240VDC 192VDC/240VDC
Float Charge Voltage 220Vdc/274Vdc 220Vdc/274Vdc 220Vdc/274Vdc
Cyclic Charge Voltage 230Vdc/288Vdc 230Vdc/288Vdc 11230Vdc/288Vdc
Max.Charge Current 4.0A 4.0A 4.0A
Rated dischargeCurrent 48A/39A 73A/58A 96A/77A
General Parameters Display LED+LCD LED+LCD LED+LCD
  Efficency AC: >90%; Batt: >86% AC: >91%; Batt: >87% AC: >91%; Batt: >87%
  Noise <60dB
  Working altitude 1000m
  Relative Humidity 0~95%
  Storage Temperature -25℃ ~ +55℃ ( Battery: -20℃ ~+40℃ )
  Working Temperature -10℃ ~+40℃
  Cooling Air-cooled
  Protection Class Ip20
  Input Socket/Terminal Terminal Terminal Terminal
  Output Sockct/Terminal Terminal Terminal Terminal
  Dimensions(L*W*Hmm) 592x250x826 592x250x826 592x250x826
  Net Weight(kg) 38kg 40kg 40kg
Protections Over-temp.protection Radiator temperature>80℃ protection, <60℃ recovery
Direct bus under / Over-voltage Under-voltage : 200V, Over-voltage: 430V
Output under / Over Voltage Under-voltage : 170V, Over-voltage: 265V
Over-load AC: switch to bypass and alarm, Battery: alarm and delay shutdown after overload
Others Software function Setting Various working modes and operating parameters can be set through LCD Display
Self-Starting Shut down after battery under-voltage protection , then resume automatically after AC ON.
ECO function ECO function with bypass priority
Automatic shutdown After the battery under-voltage protection, the auxiliary power will be turned off automatically after 5S
Battery cold start With the function of battery cold start inverter
Interface RS232/485/CAN/Ethernet
Electromagnetic Compatibility Meet the relevant requirements of GB7260.2 C2Class

 

 